WIRING SCHEMATIC

PHOTONS → BUSBAR · v8 BUYLIST-SYNCED · 2026-11-12

RUN 58VDC/210A · companion to BUYLIST.SYS v11.0 · phone-first Kafkas · gPV 20A before panels — NO EXCEPTIONS

FULL DC TRAIN — TOP TO BOTTOM

Array → combiner/SPD → 30m twisted bundles → wall boxes → MPPTs → shared bus → packs + Studers

STRING 1 P1 450W P2 450W 2S · ~48V NOM STRING 2 P1 450W P2 450W 2S · ~48V NOM STRING 3 P1 450W P2 450W 2S · ~48V NOM STRING 4 P1 450W P2 450W 2S · ~48V NOM STRING 5 P1 450W P2 450W 2S · ~48V NOM STRING 6 P1 450W P2 450W 2S · ~48V NOM STRING 7 P1 450W P2 450W 2S · ~48V NOM STRING 8 P1 450W P2 450W 2S · ~48V NOM COMBINER 1 20A gPV 20A gPV SD63 SW 63A SPD T2 · Uc ≥150V SURGES DIE HERE COMBINER 2 20A gPV 20A gPV SD63 SW 63A SPD T2 · Uc ≥150V SURGES DIE HERE COMBINER 3 20A gPV 20A gPV SD63 SW 63A SPD T2 · Uc ≥150V SURGES DIE HERE COMBINER 4 20A gPV 20A gPV SD63 SW 63A SPD T2 · Uc ≥150V SURGES DIE HERE EARTH BUS — FRAMES + RAILS + SPD BONDED (≥6 mm²) EARTH ROD 4× TWISTED PAIRS — 25 mm² BASELINE + AND − TAPED TOGETHER — SEPARATION = PICKUP LOOP BULKHEAD PLATE — ONE PENETRATION · ALL CABLES + SHIELDS BOND HERE WALL BOX #1 — PV SIDE · SD63 RACK DISCONNECTS SD63 63A in: 10 mm² from combiners · out: 16 mm² twisted → MPPTs SD63 63A in: 10 mm² from combiners · out: 16 mm² twisted → MPPTs SD63 63A in: 10 mm² from combiners · out: 16 mm² twisted → MPPTs SD63 63A in: 10 mm² from combiners · out: 16 mm² twisted → MPPTs BLUESOLAR150/60 BLUESOLAR150/60 BLUESOLAR150/60 BLUESOLAR150/60 WALL BOX #2 — MPPT OUT isolate any MPPT without dropping the fleet NH00 80A aRSD63 SW 63A NH00 80A aRSD63 SW 63A NH00 80A aRSD63 SW 63A NH00 80A aRSD63 SW 63A SHARED DC BUSBAR · LEGRAND 500A + − trunk: 2× 95 mm² or 120–150 mm² DISCONNECT DISCONNECT DISCONNECT STUDER XTH8000-48 STUDER XTH8000-48 STUDER XTH8000-48 95 mm² tap + DC disconnect EACH · 21 kVA total · existing NH1 250A aR MAIN BACKSTOP · 1+1 SPARE PACK 2 — RESERVED DATOUBOSS 314Ah48V · 16 kWh210A BMS PACK 3 — RESERVED INTERIM: 1 PACK LIVE — packs 2–3: top-balance, bolt to busbar, done · v8: NH1 250A aR main · isolation = SD63 racks EMC DOCTRINE — MEASURE FIRST, FILTER SECOND CMC: wind + and − together, same direction, 2–3 turns · sendust covers 100–500 kHz fundamental Star ground — one point, no loops · DC never parallels coax — cross at 90°
CYAN = HARVEST — STRINGS + MPPTS MAGENTA = COPPER RUNS — WIRES · GAUGES · TRUNK ORANGE = FUSES — gPV 20A · NH00 80A · NH1 250A · STUDER DISCONNECTS BLUE = SWITCHES — SD63 RACKS + ISOLATORS (NO TRIP) YELLOW = SURGE GEAR — SPD T2 · SURGES DIE HERE LIGHT PURPLE = CLICK FOR INFO (HOTSPOTS) GREEN = POWER PATH · FAT LINE (7px) = EARTH BUS

OVERCURRENT ROLES — THE MENTAL MODEL

Hardware quantities, SKUs and prices: the dedicated SHOPPING LIST — BUY ORDER v10.5 page is the source of truth

Why the chain looks the way it does: every layer has ONE job, and the jobs get more brutal as you move toward the battery

▚ THE ONE SENTENCE: a FAULT is current escaping its path — the defense is a ladder of devices, each rated to kill a bigger monster than the last, each placed so the one behind it never faces the monster alone.

THE THREE JOBS — learn these and every device on the schematic snaps into place

JobDevice familyWhat it actually doesWhy it can't do the other jobs
EXECUTEfuses — gPV 20A · NH00 80A aR · NH1 250A aRmelts open when current exceeds its rating for long enough. aR class melts in milliseconds — before the copper heats — because semiconductors and fat battery shorts give it no time to sparea fuse dies doing its job. It can't be reset, can't be switched daily, and can't tell a fault from a thunderstorm-day surge unless the rating is chosen lean (that's sizing, below)
ISOLATEswitches — SD63 racks & isolators · Studer DC disconnectsopens a circuit on YOUR command, for service or emergency. It carries current all day, interrupts it cleanly (DC-rated contacts), and never acts on its owna switch has no fault detection and no interruption muscle for a dead-short — asking a breaker to clear a 48V bank short means watching it arc until it burns
CLAIM EARTHsurge gear — SPD T2 · the ELEMKO rodgives lightning a designated exit: the SPD clamps a spike and dumps it down the 7px earth bus to ONE rod, so it never routes through your MPPTs insteaddoes nothing against overcurrent — a surge is over in microseconds; fuses barely twitch. Different monster, different weapon

THE LADDER, WALKED — trace one fault and you know the whole system

1 · a string faults at the panel: its gPV 20A fuse at the combiner melts — ONLY that string opens, the other 11 keep harvesting. The fuse sits AT the source because a fault must be stopped before it enters the 30m wire run.

2 · an MPPT leg faults: the NH00 80A aR in box #2 clears in milliseconds — fast enough that the 25mm² leg never warms. The blue SD63 next to it doesn't even notice; its job starts only when a human walks over and pulls it for service.

3 · the bank itself shorts: three 314Ah packs can deliver thousands of amps. This is NH1 territory: the 250A aR main is the ONLY device on the page rated to interrupt that monster without a sustained arc — it sacrifices itself instantly, and the 95mm² trunk (good for ~400A+) never leaves its temperature corridor.

4 · a pack needs service: no fuse moves. You open the SD63 rack / disconnect, the pack goes quiet while the NH1 stays armed protecting the other two. Executing and isolating never borrow each other's uniforms.

THE SIZING LOGIC — why each number is that number

▚ THE ONE-LINE COLOR CODE orange kills · blue isolates · yellow redirects to earth · cyan harvests · magenta carries. If a device's color surprises you, that's the schematic asking you to double-check it.

INTERIM MODE — SINGLE PACK OPERATIONS

Until packs #2 & #3 land — same hardware, reined-in limits

▚ NOTE ON COMBINER #4 LID: "OPEN — ACTIVATES WITH PACK 3"

CORRECTIONS FOLDED IN — V8.0 → V8.1 STRING ACCOUNTING (12 Nov 2026)

Rule 28 append · fleet math checked against the 150/60-Tr specs: nominal 3,440W @48V · max PV Isc 50A — "higher current may damage controller"